CH3-40.5KV/660(improved) contact box (TEE)
Detailed description

summary


The contact box adopts epoxy resin structure, which is used for various handcart type switch cabinets to play the role of insulation isolation and connection transition. The installation center distance is 250mm, the rated voltage is 10kV, and the current is 2500A ~ 3150A. Under the rated current, the temperature rise at the end of the outlet should not exceed 65 ℃ under long-term operation.


Model and its meaning

1.jpg

Conditions of use


1. The altitude shall not exceed 1000m;


2. Ambient temperature + 40 ℃ ~ 10 ℃;


3. When the air temperature is + 20 ℃, the relative humidity is more than 95%;


4. No gas, steam, dust and other explosive and corrosive media seriously affecting the insulation of contact box.


Technical data and requirements


1. The contact box and the contact to the ground shall be able to withstand the power frequency test voltage (validity) of 42KV for 5 minutes, and the lightning impulse (peak value) of 75KV;


2. Under the rated current, the temperature rise at the end of the outgoing line shall not exceed 65 ℃ under long-term operation of the contact box;


3. See the attached figure for the shape and installation dimension of the contact box.